PowerGenix Nickel-Zinc Charge Procedure
Two Step Charge
- Constant Current: From 1.0 to 2.0 Amps to 1.9V/Cell
- Constant Voltage: 1.9V/Cell to Current < 90mA
Fault Conditions
- Total charge time exceeds 2.5 hrs
- Temperature of the cell rises by more than 15C
- Voltage is less than 1.6V
Notes: For Laboratory Testing: Non temperature compensation at 25°C +/_ 3 degrees
Temperature Compensated Charge Procedure
Two Step Charge
- Temperature Compensated Voltage (TCV) = 1.90 - (0.003 x (T-25ºC) V/Cell
- Constant Current 2A to TCV
- Constant Voltage TCV to I < 90 mA
Fault Conditions
Stop Charge if the any of the following conditions occur:
- Total charge time exceeds 2.5 hrs
- Temperature of the cell rises by more than 15ºC
- Temperature of the cell exceeds 40ºC
- Voltage is less than 1.6V
Charge Characteristics at 25°C
Maintenance Charge Procedure
Recharge cell/pack per Standard Charge Procedure if:
- Volts per cell < 1.68 V
- Time since last full charge > 30 days